LED wall power calculator

Total power is panels × watts per panel, and current is watts ÷ volts. Panels per circuit = volts × breaker amps × 80 % ÷ watts per panel, rounded down. Plan circuits on the panel's maximum draw, not its typical one.

Total power

27.60 kW

120.0 A at 230 V

Heat

94,171 BTU/h

at full draw

Panels per circuit

12

2,944 W per 16 A circuit

Circuits

10

at least

Feeds

1 × 63 A three-phase

Worst line 48.0 A of 50.4 A allowed · 43.5 kW per feed

The formula

Total power (W) = panels × max watts per panel
Current (A) = total power ÷ volts
Circuit (W) = volts × breaker amps × 0.8
Panels per circuit = circuit W ÷ watts per panel, rounded down
Circuits = panels ÷ panels per circuit, rounded up
Heat (BTU/h) = watts × 3.412

The circuit count is the minimum. In LED Planner's Energy page each circuit follows your power cabling path across the wall, which can take one or two more, and the feed lines are balanced circuit by circuit.

Worked example

120 panels of ROE CB5 (230 W max), the 20 × 6 wall from the resolution calculator:

Total = 120 × 230 W = 27,600 W (94,171 BTU/h)
230 V = 27,600 ÷ 230 = 120.0 A
16 A = 230 × 16 × 0.8 = 2,944 W → 12 panels per circuit → 10 circuits
Feed = 1 × 63 A CEE three-phase (43.5 kW at 100 %)
120 V = 27,600 ÷ 120 = 230.0 A
20 A = 120 × 20 × 0.8 = 1,920 W → 8 panels per circuit → 15 circuits
Feed = 1 × 100 A Cam-Lok three-phase, 120/208 V

FAQ

Should I plan on typical or maximum panel power?

Size circuits and distro on the maximum draw: a full-white frame pulls it, and a tripped breaker takes the wall down mid-show. Typical draw is right for generator fuel and air-conditioning estimates.

Why load circuits to 80 %?

In North America the NEC limits continuous loads (three hours or more) to 80 % of the breaker rating, and a show day is a continuous load. Elsewhere it isn't the same code rule, but most crews keep the same headroom.

How many LED panels fit on one circuit?

Volts × breaker amps × 0.8 ÷ watts per panel, rounded down. At 230 V on a 16 A breaker that's 2,944 W, so 12 panels of 230 W. At 120 V on 20 A it's 1,920 W, so 8 of the same panels.

What about 208 V in North America?

On a 120/208 V three-phase service, panels can run line to line at 208 V: more panels per circuit, but every circuit loads two lines. LED Planner balances them with the real phasor sums (√3 × the current when balanced), not a straight split.

Why did a breaker trip when the wall switched on?

Switch-mode supplies draw an inrush spike at power-on, which can trip a breaker loaded close to its limit even when the running load fits. Power the wall up in sections, not all at once.